APPLICATION |
- Fire damper prevents smoke and fire propagation through the air ducts of ventilation and air conditioning systems in case of fire.
- Mounted in the ventilation ducts laid through fireproof walls and ceilings.
- Fire resistance rating is EIS 120.
|
DESIGN |
- Consists of a galvanized steel casing (1), blades from insulation material (calcium silicate) and fireproof material (2), thermic release mechanism (3) activated at 70°С, silicone seal (4) and spring (5).
- The fire damper is open while operation.
- In case of fire the thermoelement melts at 70°С and the spring moves the blade to closed position.
|
DIMENSIONS |
- Dn = 100, 125, 150, 160, 180, 200 mm.
|
MOUNTING |
- Install the fire damper in such a way so that the release mechanism and inspection hole are on the side of the wall or ceiling for easy inspection of the thermic release mechanism and its internal part.
- Building the damper into brick and concrete walls or gypsum plates with the relevant fire resistance rating is allowed.
- To preserve the casing shape during mounting use wooden supports to prevent possible casing deformation and remove them after the final mounting.
- Warning!!! Do not install the fire dampers in high-explosive environment or in ventilation systems designed for exhaust of explosive air-gas mixtures.
|
|
|
|
|
|
DESIGN AND DIMENSIONS |
|
|
|
RECOMMENDED POSITIONS OF FIRE DAMPER |
|
|
|
WOODEN SUPPORTS DURING MOUNTING |
|
|
|
DOWNLOADS |
|
|