VENTS AOW 25
Air unit with the water heat exchanger. Maximum capacity - up to 2200 m³/h.
- Description
- Characteristics
- Downloads
- Dimensions
- ADDITIONAL TECHNICAL DATA
- Designation key
- Accessories
Description
Description
APPLICATION | CONTROL AND REGULATION |
|
|
DESIGN | |
|
|
MOUNTING | MOTOR |
|
|
AIR HEATING (COOLING) ADVANTAGES: | |
|
|
VENTS AOW unit greenhouse heating example | VENTS AOW unit garage cooling example |
VENTS AOW unit stock house heating example |
Characteristics
Characteristics
Parameter |
AOW 25 |
Measurement unit |
---|---|---|
Voltage | 230 | V |
Frequency | 50 | Hz |
Fan power | 136 | W |
Fan current | 0.6 | A |
RPM | 1350 | min-1 |
Sound pressure level at 3 m | 53 | dBА |
Maximum heat medium temperature | 100 | °С |
Protection rating | IP 44 | - |
Number of water coil rows | 2 | - |
Weight | 37 | kg |
Insulation class | F | - |
Air reach distance | 9 | mm |
Files archieve
Downloads
Select document type
"Control unit for air heating (cooling) unit with water heat exchanger - UWT series" user's manual 06-2017 (V52-1EN-02) (pdf 383.75Kb)
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
B | 680 | mm |
B1 | 785 | mm |
H | 605 | mm |
H1 | 468 | mm |
L | 360 | mm |
L1 | 286 | mm |
K | G 3/4'' | mm |
ADDITIONAL TECHNICAL DATA
ADDITIONAL TECHNICAL DATA
TECHNICAL DATA FOR HEATING MODE
Model | Air flow [m3/h] | Inlet air temp. [°С] | Temperature difference 90/70 °С | Temperature difference 80/60 °С | Temperature difference 70/50 °С | Temperature difference 60/40 °С | ||||||||||||
Power [kW] | Outlet air temp. [°С] | Water flow [m3/h] | Water pressure loss [kPa] | Power [kW] | Outlet air temp. [°С] | Water flow [m3/h] | Water pressure loss [kPa] | Power [kW] | Outlet air temp. [°С] | Water flow [m3/h] | Water pressure loss [kPa] | Power [kW] | Outlet air temp. [°С] | Water flow [m3/h] | Water pressure loss [kPa] | |||
AOW 25 | 2200 | -15 | 34.5 | 26.0 | 1.51 | 7.5 | 30.4 | 21.2 | 1.30 | 6.0 | 26.0 | 16.0 | 1.19 | 4.6 | 22.0 | 11.0 | 1.01 | 3.4 |
-10 | 32.0 | 29.0 | 1.40 | 6.6 | 28.3 | 24.3 | 1.22 | 5.3 | 24.0 | 19.2 | 1.12 | 4.0 | 20.0 | 14.0 | 0.90 | 2.8 | ||
-5 | 30.0 | 32.0 | 1.30 | 5.8 | 26.2 | 27.4 | 1.19 | 4.6 | 22.0 | 22.0 | 1.01 | 3.4 | 18.0 | 17.0 | 0.79 | 2.3 | ||
0 | 28.0 | 35.0 | 1.19 | 5.2 | 24.1 | 30.4 | 1.12 | 4.0 | 20.0 | 25.0 | 0.90 | 2.8 | 16.0 | 20.0 | 0.68 | 1.8 | ||
5 | 26.2 | 38.5 | 1.19 | 4.5 | 22.1 | 33.3 | 1.01 | 3.3 | 18.0 | 28.0 | 0.79 | 2.3 | 14.0 | 22.0 | 0.61 | 1.4 | ||
10 | 24.2 | 41.4 | 1.12 | 3.9 | 20.1 | 36.1 | 0.94 | 2.8 | 15.9 | 30.6 | 0.68 | 1.9 | 12.0 | 25.0 | 0.50 | 1.0 | ||
15 | 22.1 | 44.2 | 1.01 | 3.3 | 18.1 | 38.8 | 0.90 | 2.3 | 13.8 | 33.0 | 0.61 | 1.4 | 9.0 | 27.0 | 0.40 | 0.7 |
TECHNICAL DATA FOR COOLING MODE
Model | Air flow [m3/h] | Inlet air temp. [°С] | Temperature difference 7/12 °С | |||
Power [kW] | Outlet air temp. [°С] | Water flow [m3/h] | Water pressure loss [kPa] | |||
AOW 25 | 2200 | 35 | 9.1 | 26.0 | 1.6 | 7.5 |
30 | 5.8 | 22.5 | 1.0 | 6.1 | ||
25 | 3.2 | 21.0 | 0.6 | 2.1 | ||
20 | 2.0 | 18.0 | 0.3 | 0.9 |
Designation key
Designation key
Series | Rated power [kW] |
VENTS AOW VENTS AOW1 |
25; 30; 45 |
Accessories
Accessories
Air heating unit model | Control unit | Digital thermostat | Mounting accessories | ||
with sensor display | with LCD display | Mounting angles | Mounting brackets | ||
AOW 25 | UWT-1E | TST-1-300 TSTD-1-300 |
RTS-1-400 RTSD-1-400 |
MKP-AOW | MK-AOW 25 |
AOW1 25 | MK-AOW1 25 | ||||
AOW 30 | MK-AOW 30 | ||||
AOW1 30 | MK-AOW 25* | ||||
AOW 45 | MK-AOW 45 | ||||
AOW1 45 | MK-AOW 30* |
* The cross pieces between the MK-AOW mounting brackets are not applicable in case of AOW1 mounting.