VENTS OV 4D 500
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- ADDITIONAL TECHNICAL DATA
- Designation key
- BIM
APPLICATIONS | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
Parameter |
OV 4D 500 50 Hz |
OV 4D 500 60 Hz |
Measurement unit |
---|---|---|---|
Phase | 3 | 3 | ˜ |
Voltage | 400 | 400 | V |
Frequency | 50 | 60 | Hz |
Sound pressure level at 3 m distance | 60 | 60 | dBА |
Power consumption | 450 | 370 | W |
RPM | 1300 | 1605 | min-1 |
Protection rating | IP 24 | IP 24 | - |
Maximum air capacity | 6570 | 6230 | m³/h |
Weight | 14.0 | 14.0 | kg |
Current | 0.9 | 0.7 | A |
- Selection method:
- Air flow:
- Pressure:
- Air flow: --
- Pressure: ---
Parameter | Value | Measurement unit |
---|---|---|
∅D | 520 | mm |
∅d | 11 | mm |
B | 655 | mm |
B1 | 615 | mm |
L | 250 | mm |
Sound-power level, A-weighted | Gen. | Octave-frequency band [Hz] | LpA, 3 m dBA | LpA, 1 m dBA | ||||||||
dBA | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||||
LwA to environment | dBA | 81 | 51 | 63 | 70 | 74 | 75 | 76 | 71 | 62 | 60 | 70 |
ŋ, [%] | MC | EC | N | VSD | [kW] | [A] | [m3/h] | [Pа] | [n/min-1] | SR |
35.5 | A | Static | 43.9 | No | 0.478 | 0.9 | 4988 | 120 | 1305 | 1 |
Series and modification | Motor modification | Dimension type | |
Number of poles | Phase | ||
VENTS OV: square mounting plate | 2 4 6 8 |
E: single phase D: three phase |
200; 250; 300; 350; 400; 450; 500; 550; 630, 710, 800 |
ErP data | |
Overall efficiency | ŋ, [%] |
Measurement category | MC |
Efficiency category | EC |
Efficiency grade | N |
Variable speed drive | VSD |
Power | [kW] |
Current | [A] |
Air flow | [m3/h] |
Static pressure | [Pа] |
Speed | [n/min-1] |
Specific ratio | SR |