VENTS PVZ 800x500
- Description
- Characteristics
- Downloads
- Dimensions
- Additional diagrams
- Legend
Description
Description
APPLICATIONS | DESIGN |
|
|
OPERATING LOGIC OF THE AIR CURTAIN | |
|
|
OVERALL DIMENSIONS: |
PVZ 600x350 | PVZ 700x400 | PVZ 800x500 | PVZ 900x500 | |
B, [mm] | 600 | 700 | 800 | 900 |
L, [mm] | 350 | 400 | 500 | 500 |
H1, [mm] | from 2.0 up to 5.0 | |||
H2 (curtain with no heating) [mm] | 1150 | 1300 | 1450 | 1520 |
H2 (curtain with water heater) [mm] | 1350 | 1500 | 1650 | 1720 |
H2 (curtain with electric heater) [mm] | 1350 | 2050 | 1960 | 2270 |
FAN MOTOR |
MOUNTING |
|
|
Characteristics
Characteristics
Parameter |
PVZ 800x500 |
Measurement unit |
---|---|---|
Voltage | 400 | V |
Fan power | 2790 | W |
Fan current | 5.18 | A |
Air capacity | 6200 | m³/h |
Air capacity | 6200 | m³/h |
H2 (air curtain without heating) | 1450 | mm |
H2 (air curtain with water heating) | 1650 | mm |
Phase | 3 | - |
H2 (air curtain with electric heater) | 1960 | mm |
Electric heater power | 36000 | W |
Electric heater current | 52 | A |
Fan type | - | |
Filter type | - | |
Type of water heater | - | |
Type of electric heater | - | |
Heating | without heating | - |
Width | 800 | mm |
Height | 500 | mm |
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
B | 800 | mm |
H1 | от 2.0 до 5.0 | mm |
L | 500 | mm |
Additional diagrams
Additional diagrams
Air curtain selection procedure
- Determine the required air curtain orientation (e.g., vertical).
- Determine the required heating type (W - water type, E - electrical type, N - no heating)
- The nomographic chart 1 shows the effective reach distance of the curtain (1) (e.g., 3.5 m; for vertical orientation that value is equal to the door opening width).
- For the outlet air stream speed from the curtain draw a perpendicular line down to the nomographic chart 2 (e.g., 13.9 m/s).
- Using the nomographic chart 3 determine the outlet slit of the air curtain (3) (e.g., 2.5 m; for vertical orientation that is equal to the height of the door opening).
- The nomographic chart 4 shows the minimum required air capacity (lines 4 and 5, e.g., 4400 m3/h).
- The intersection of curves 5 and 6 lies at one of the colour fields of the design chart 5. The field of the point location detrmines the standard size of the air curtain (e.g., 800х500).
- Projection of curve along the parable 7 up to the point of intersection with the curve that limits the colour field from above, determines the operating point of the air curtain. The air capacity 4800 m3/h which is somewhat above the minimum required air capacity refers to the effective operating point.
Legend
Legend
Series | Standard size | Heater type | Slit outlet section length | |||
---|---|---|---|---|---|---|
PVZ |
600х350 700х400 800х500 900х500 |
W - water E - electric N - no heater |
2; 2,5; 3; 3,5; 4; 4,5; 5 |