VENTS TF230
- Description
- Characteristics
- Downloads
- Dimensions
- Wiring plan
Description
Description
APPLICATION | DESIGN |
|
|
Characteristics
Characteristics
Parameter |
TF230 |
Measurement unit |
---|---|---|
Voltage ![]() |
230 AC 50/60 Hz | V |
Frequency ![]() |
50/60 | Hz |
Nominal voltage range ![]() |
85...265 AC | V |
Rated power ![]() |
4 (max. I 150 mA at t = 10 ms) | VA |
Power consumption in operation ![]() |
2 | W |
Power consumption at rest ![]() |
1.3 | W |
Connecting cable ![]() |
1 m long, 2 x 0.75 mm² | - |
Rotation direction ![]() |
determined by L/R positioning | - |
Torque motor ![]() |
2, nominal voltage | Nm |
Torque spring ![]() |
2 | Nm |
Rotation angle: ![]() |
max. 95°, adjustable 37…100 % with a mechanical end stop | - |
Running time motor ![]() |
40…75 (0…2 Nm) |
sec |
Running time spring ![]() |
< 25 at -20…50 °C |
sec |
Service life ![]() |
60 000 switching operations | - |
Protection rating ![]() |
IP 42 | - |
Electrical protection class ![]() |
III low voltageII totally insulated | - |
Operation temperature ![]() |
-30...+50 | °С |
Storage temperature ![]() |
-40…+80 | °С |
Ambient humidity ![]() |
95 %, no condensation | - |
Noise level motor ![]() |
50 | dBА |
Noise level spring ![]() |
~62 | dBА |
Maintenance ![]() |
not required | - |
Weight ![]() |
0.6 | kg |
Files archieve
Downloads
Select document type
Dimensions
Characteristics
![VENTS TF230](/uploads/productCard/8708_schema.jpg)
Parameter | Value | Measurement unit |
---|
Wiring plan
Wiring plan