VENTS VK 315 EC
Inline centrifugal fan in plastic casing with the air capacity up to 1500 m³/h.
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional characteristics
- Designation key
Description
Description
APPLICATIONS | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
VENTS VK EC fan kitchen ventilation example |
Characteristics
Characteristics
Parameter |
VK 315 EC |
Measurement unit |
---|---|---|
Voltage | 1~230 | V |
Frequency | 50/60 | Hz |
Sound pressure level at 3 m distance | 48 | dBА |
Power consumption | 165 | W |
Maximum air capacity | 1500 | m³/h |
Current | 1.15 | A |
EC motor | yes | - |
RPM | 2500 | min-1 |
Max. transported air temperature | -25 +60 | °С |
Protection rating | IP X4 | - |
Design | centrifugal | - |
Duct diameter | 315 | mm |
Weight | 4.9 | kg |
Casing material | plastic | - |
SEC Class | - | - |
Duct | for round air ducts | - |
Mounting | Inline | - |
* | To meet the requirements of ErP 2018, a speed controller and local demand control typology must be applied (connect a sensor). | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 315 | mm |
ØD1 | 400 | mm |
B | 414 | mm |
L | 276 | mm |
L1 | 40 | mm |
L2 | 55 | mm |
L3 | 40 | mm |
Additional characteristics
Additional characteristics
Point on the diagram | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | 18 | 19 | 20 |
Power [W] | 149 | 164 | 165 | 158 | 94 | 106 | 112 | 104 | 74 | 83 | 90 | 84 | 37 | 39 | 45 | 41 | 17 | 19 | 19 | 17 |
ƞ, [%] | MC | EC | N | VSD | [kW] | [A] | [m3/h] | [Pa] | [RPM] | SR |
42.3 | А | Static | 62.1 | No | 0.164 | 1.14 | 1021 | 247 | 2472 | 1 |
Sound power level, A-filter applied | Sound pressure level at 3 m distance, A-filter applied | Sound pressure level at 1 m distance, A-filter applied | ||||||||||
Sound power level, A-weighted | Gen. | Octave frequency band [Hz] | ||||||||||
Hz | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | LpA, 3 m [dBA] | LpA, 1 m [dBA] | ||
LwA to inlet | dBA | 86 | 51 | 73 | 71 | 75 | 81 | 82 | 77 | 68 | 66 | 76 |
LwA to outlet | dBA | 87 | 55 | 66 | 76 | 73 | 81 | 84 | 77 | 69 | 67 | 77 |
LwA to environment | dBA | 69 | 30 | 48 | 56 | 62 | 64 | 64 | 56 | 49 | 48 | 58 |
Designation key
Designation key
Series | Duct diameter | Motor | Options |
VENTS VK EC |
100; 125; 150; 200; 250; 315 |
ЕС - synchronous electronically commutated motor |
U: speed controller with electronic thermostat and temperature sensor integrated into the air duct. Equipped with power cord and IEC C14 electric plug. Un: speed controller with electronic thermostat and external temperature sensor fixed on 4 m cable. Equipped with power cord and IEC C14 electric plug. P: built-in smooth speed controller and power cable with IEC C14 electric plug. R: power cord with IEC C14 electric plug. |
ErP data | |
Overall efficiency | η, [%] |
Measurement category | MC |
Efficiency category | EC |
Efficiency grade | N |
Variable speed drive | VSD |
Power | [kW] |
Current | [A] |
Air flow | [m3/h] |
Static pressure | [Pa] |
Speed | [n/min-1] |
Specific ratio | SR |