VENTS VKMI 250 Q
- Description
- Characteristics
- Downloads
- Dimensions
- Additional diagrams
- Legend
APPLICATIONS | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
The fan with electronic temperature and control module (U option)
|
|
|
|
|
|
Control logic of the fan with the electronic temperature and speed control module
|
|
|
|
There are two switch delay patterns for various cases: | |
|
|
Parameter |
VKMI 250 Q |
Measurement unit |
---|---|---|
Highpowered motor | no | - |
Low-powered motor | no | - |
Voltage | 230 | V |
Frequency | 50 | Hz |
Sound pressure level at 3 m distance | 46 | dBА |
Power consumption | 158 | W |
RPM | 2315 | min-1 |
Maximum air capacity | 1190 | m³/h |
Current | 0.69 | A |
Max. transported air temperature | -25 +50 | °С |
Protection rating | IP X4 | - |
Design | centrifugal | - |
Duct diameter | 250 | mm |
Weight | 13.4 | kg |
Sound- and heat-insulated casing | yes | - |
Casing material | polymer coated steel | - |
SEC Class | - | - |
Duct | for round air ducts | - |
Type | supply and exhaust | - |
Mounting | Inline | - |
Parameter | Value | Measurement unit |
---|---|---|
A | 625 | mm |
∅D | 248 | mm |
B | 410 | mm |
H | 320 | mm |
C | 389 | mm |
h | 250 | mm |
c | 250 | mm |
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 68 | 46 | 57 | 60 | 65 | 62 | 58 | 60 | 54 | ||||||||||
LwA to outlet | dBA | 64 | 37 | 50 | 54 | 55 | 57 | 55 | 58 | 50 | ||||||||||
LwA to environment | dBA | 51 | 37 | 48 | 44 | 40 | 31 | 33 | 43 | 38 |
Series fan | Air duct diameter, mm | Options |
VENTS VKMI |
100; 125; 150; 160; 200; 250; 315 | U – speed controller with electronic thermostat and temperature sensor integrated into the air duct. Equipped with power cord and IEC C14 electric plug. Temperature-based operation logic. U1 – speed controller with electronic thermostat and temperature sensor integrated into the air duct. Equipped with power cord and IEC C14 electric plug. Timer-based operation logic. Un – speed controller with electronic thermostat and external temperature sensor fixed on 4 m cable. Equipped with power cord and IEC C14 electric plug. Temperature-based operation logic. U1n – speed controller with electronic thermostat and external temperature sensor fixed on 4 m cable. Equipped with power cord and IEC C14 electric plug. Timer-based operation logic. P – built-in smooth speed controller and power cord with IEC C14 electric plug. R – power cord with IEC C14 electric plug. Q – low-powered motor. S – high-powered motor. K – versatile fixing bracket. |
ErP data | |
Overall efficiency | η,[%] |
Measurement category | MC |
Efficiency category | EC |
Efficiency grade | N |
Variable speed drive | VSD |
Power | [kW] |
Current | [A] |
Air flow | [m3/h] |
Static pressure | [Pa] |
Speed | [n/min-1] |
Specific ratio | SR |