VENTS VKPF 6E 600*300
Inline centrifugal fan. Maximum capacity - 2260 m3/h.
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional diagrams
- Designation key
Description
Description
APPLICATIONS | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
VENTS VKPF fan warehouse ventilation example |
Characteristics
Characteristics
Parameter |
VKPF 6E 600*300 |
Measurement unit |
---|---|---|
Phase | 1 | ˜ |
Voltage | 230 | V |
Frequency | 50 | Hz |
Sound pressure level at 3 m distance | 50 | dBА |
Air capacity | 2260 | m³/h |
Power consumption | 419 | W |
Current | 2.05 | A |
RPM | 870 | min-1 |
Protection rating | IP X4 | - |
Design | centrifugal | - |
Transported air temperature | -20 … +70 | °С |
Weight | 35 | kg |
Number of poles | 6 | - |
Sound- and heat-insulated casing | no | - |
Casing material | galvanized steel | - |
Width | 600 | mm |
Height | 300 | mm |
Duct | for rectangular air ducts | - |
Mounting | Inline | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
В | 600 | mm |
B1 | 620 | mm |
B2 | 640 | mm |
H | 300 | mm |
H1 | 320 | mm |
H2 | 340 | mm |
H3 | 375 | mm |
L | 680 | mm |
Additional diagrams
Additional diagrams
Sound-power level | Octave-frequency band [Hz] | |||||||||
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |
LwA to inlet | dBA | 69 | 62 | 64 | 61 | 56 | 62 | 62 | 55 | 52 |
LwA to outlet | dBA | 74 | 53 | 63 | 58 | 67 | 67 | 63 | 61 | 56 |
LwA to environment | dBA | 57 | 49 | 47 | 56 | 45 | 45 | 49 | 37 | 34 |
Designation key
Designation key
Series | Motor modification | Flange diameter [W*H] | |
Number of poles | Phase | ||
VENTS VKPF | 4 6 |
E: single phase D: three phases |