VENTS Non-insulated air ducts Thermovent Aero Flex series
Description
Description
DESCRIPTION |
FEATURES |
- Double-layer stainless steel spiral-seam air ducts with high aerodynamic and strength characteristics.
|
- Made of incombustible corrosion-resisting stainless steel band.
- Increased thermal resistance (up to 800°С).
- Specially designed high-quality locks ensure high seam tightness and total air tightness of the ducts.
- Smooth internal surface ensures low dynamic losses.
- Low weight and easy mounting.
|
RECOMMENDED APPLICATION |
- Applied in residential and industrial ventilation, air conditioning and heating systems with the maximum pressure 10 000 Pa.
- For supply and exhaust ventilation.
- Applied in the systems of hot air removal from boiler houses and smoke exhaust systems.
|
TECHNICAL DATA: |
|
|
|
Item |
Thermovent Aero Flex |
Diameter range [mm] |
50/60/80/100/110/120/130/135/140/150/160/180/200/250/300/350/400 |
Material |
Stainless steel |
Number of layers |
|
2 |
Total thickness [μm] |
Internal layer |
100 |
External layer |
100 |
Operating temperature range [°C] |
|
-30 +800 |
Maximum air speed [m/s] |
|
30 |
Maximum operating pressure [Pa] |
|
10000 |
Minimum bend radius [mm] |
up to Ø 200 mm |
4D |
above Ø 200 mm |
4.5хD |
Length [m] |
|
1; 2; 3; 6 |
|
|
PRESSURE LOSS DIAGRAM PER 1 M STRETCHED AIR DUCT |
CALCULATION EXAMPLE: |
|
|
|
- Select a curve that matches the air duct diameter [mm], 200 mm in this case.
- Find the intersection point of this line with the vertical line of the required air flow in m3/h, 500 m3/h in this case.
- The horizontal line that shows the pressure loss in Pa per 1 m straight air duct crosses this intersection point.
- Multiply pressure loss value (2.4 Pa/m at 20°С) by total air duct length to get the total pressure loss value. To calculate pressure loss in case of bends consider each bend as extra air duct meter.
|