Login

Privacy Policy (GDPR)
Authorization
Not registered yet? Take advantages of registration:
Products saving in a binding to the projects
Product consultation from our experts - Online
Registration
Signup
By using this form, you confirm that you have read the site terms of use Terms of use and completely accept the terms of use

VENTS PL-10-...-DN150

  • Description
  • Characteristics
  • Downloads
  • Dimensions
  • Designation key
  • BIM
  • Characteristics of actuators
Description
Description
APPLICATION INSTALLATION
  • A fire safety damper prevents the spread of smoke and fire via ventilation and air conditioning system ducts in the event of fire. Such units are installed in ventilation duct channels which cross fire-separation walls and ceilings. The fire resistance rating according to EN 1366-2 is EIS 60 or EIS 120.
DESIGN
  • The PL series dampers are made in the general-purpose industrial version with a minimized variety of hardware components using low-alloy galvanized steel. The flap is made of fire-resistant material (vermiculite) with thermoexpansive fireproof sealing. The duct design implies two connection ports for integration into a ventilation duct (duct system).
  • The PL-10-PKP/PL-10-PVP/PL-10-PSP series dampers are equipped with an electric actuator with a built-in return spring and thermally sensitive breaker.
  • Setting the damper to operating position (direct fire contact): remotely, via electric actuator. The damper can be set to the operating or protective position either remotely via a control panel or manually using the manual cocking handle which is always included in the standard delivery set of the electric actuator.
  • In case of the remote control panel failure, the back-up thermal breaker interrupts the power supply to the electric actuator and the return spring sets the damper to the operating position.
  • Emergency damper actuation:
    • The damper flap is set to the protective position automatically (damper unaffected by fire). The electric actuator remains energized at all times.
    • In case of an emergency actuation (direct fire contact): The electric actuator equipped with a return spring is de-energized and the damper flap is set to the operating position by means of the spring energy.
    • In case of a power failure not related to fire and its subsequent restoration at the actuator with a return spring, the damper flap returns to protective position.
  • During the fire safety damper installation make sure that the release mechanism and the inspection hole face an easily accessible side of the wall or ceiling. This will ensure convenient control of the thermally sensitive release mechanism and its internals. The damper can be embedded into brick or concrete walls with the appropriate fire resistance rating. Wooden spreader bars should be used to avoid casing deformation during the installation.
Use of wooden spreader bars during installation
  • Upon completing the installation remove the wooden spreader bars.
Recommended damper positions
  • The damper may not be installed:
    • Into air ducts and on premises rated explosion and fire safety category A and B.
    • Into air ducts of local intakes for flammable and explosive mixtures.
    • Into systems which are do not undergo periodic cleaning pursuant to the established regulations for prevention of flammable deposit buildup.
INSTALLATION RECOMMENDATIONS  
in vertical building structures in horizontal building structures
Characteristics
Characteristics
Parameter PL-10-...-DN150
Measurement unit
Duct diameter 150 mm
Weight 3.4 kg
Files archieve
Downloads
Select document type
  • Advertising and printing products
  • Certificates
  • Technical documentation
Name
"VENTS PL-10" product description 03-2023 (pdf 1.06Mb)
Download high quality image "PL-10-PKP, PL-10-PVP, PL-10-PSP" (psd 1.9Mb)
Download image "PL-10-PKP, PL-10-PVP, PL-10-PSP" for your website (png 458.44Kb)
"Dampers KP, PL" user's manual 05-2023 (V58-1EN-04) (pdf 3.41Mb)
RFA models "PL-10" (rfa 956Kb)
Dimensions
Characteristics
VENTS PL-10-...-DN150
Parameter Value Measurement unit
∅D 149 mm
L 300 mm
B 245 mm
Designation key
Designation key

BIM
BIM

Characteristics of actuators
Characteristics of actuators
MAIN TECHNICAL SPECIFICATIONS OF BELIMO ELECTRIC ACTUATORS WITH A RETURN SPRING AND A THERMAL BREAKER
Technical data Basic models
Rated operation voltage AC/DC 24 V AC 230 V
Permissible operating voltage tolerance AC 19.2…28.8 V
DC 21.6…28.8 V
АС 198…264 V
AC mains frequency 50/60 Hz
Power consumption at rest [W] 0.8 1.1
Power consumption in operation [W] 2.5 3.5
Maximum design capacity [VA] 4 6.5
Motor torque [Nm] 4
Spring torque [Nm] 3
SEC class III II
Ingress protection rating IP54
Auxiliary switches 2 pcs., single-pole, reversible 1 mA…3 (0.5) A, AC 250 V
Electric motor connection cable 1 m, 2 x 0.75 mm² (halogen-free)
Auxiliary switch connection cable 1 m, 6 x 0.75 mm² (halogen-free)
Running time spring 20 seconds at -10…+55 °С
< 60 seconds at -30…-10 °С
Running time motor < 60 s/90°
Response temperature of thermal breaker sensors Duct sensor 72 °С
Outdoor sensor 72 °С
Service life Min. 60 000 emergency positions
Technical maintenance Not required
 
MAIN TECHNICAL SPECIFICATIONS OF ZERN ELECTRIC ACTUATORS WITH A RETURN SPRING AND A THERMAL BREAKER
Technical data Basic models
Rated operation voltage AC/DC 24 V AC 100-240 V
Permissible operating voltage tolerance AC/DC 19.2…28.8 V АС 85…265 V
AC mains frequency 50/60 Hz
Power consumption at rest [W] 3
Power consumption in operation [W] 5
Motor torque [Nm] 5
Spring torque [Nm]
SEC class III II
Ingress protection rating IP54
Auxiliary switches 2 pcs., single-pole, reversible, 1 mA…3(0.5)A, AC 220 V
Electric motor connection cable 1 m, 2 x 0.5 mm² (halogen-free)
Auxiliary switch connection cable 1 m, 6 x 0.5 mm² (halogen-free)
Running time spring < 20 seconds
< 60 seconds at -30…-10 °С
Running time motor < 70 s/95°
Response temperature of thermal breaker sensors Duct sensor 72 °С
Outdoor sensor 72 °С
 
MAIN TECHNICAL SPECIFICATIONS OF SIEMENS ELECTRIC ACTUATORS WITH A RETURN SPRING AND A THERMAL BREAKER
Technical data Basic models
Rated operation voltage AC 24 V
DC 24…48 V
AC 230 V
Permissible operating voltage tolerance AC/DC ±20% АС ±15%
AC mains frequency 50/60 Hz
Power consumption at rest [W] 2 3.5
Power consumption in operation [W] 3.5 4.5
Maximum design capacity [VA] 5 7
Motor torque [Nm] 4
Spring torque [Nm] 3
SEC class III II
Ingress protection rating IP54
Auxiliary switches 2 pcs., single-pole, reversible, 6(2)A, AC 24...250 V
Electric motor connection cable 0.9 m, 2 x 0.75 mm² (halogen-free)
Auxiliary switch connection cable 0.9 m, 6 x 0.75 mm² (halogen-free)
Running time spring 15 seconds
< 60 seconds at -30…-10 °С
Running time motor 90 s/90°
Response temperature of thermal breaker sensors Duct sensor 72 °С
Outdoor sensor 72 °С
Service life 10 000 emergency positions
Technical maintenance Not required
Share your opinion

Questionnaire
Basic parameter for domestic fan selection