Characteristics of actuators
Characteristics of actuators
MAIN TECHNICAL SPECIFICATIONS OF BELIMO ELECTRIC ACTUATORS WITH A RETURN SPRING AND A THERMAL BREAKER |
Technical data |
Basic models |
Rated operation voltage |
AC/DC 24 V |
AC 230 V |
Permissible operating voltage tolerance |
AC 19.2…28.8 V DC 21.6…28.8 V |
АС 198…264 V |
AC mains frequency |
50/60 Hz |
Power consumption at rest [W] |
0.8 |
1.1 |
Power consumption in operation [W] |
2.5 |
3.5 |
Maximum design capacity [VA] |
4 |
6.5 |
Motor torque [Nm] |
4 |
Spring torque [Nm] |
3 |
SEC class |
III |
II |
Ingress protection rating |
IP54 |
Auxiliary switches |
2 pcs., single-pole, reversible 1 mA…3 (0.5) A, AC 250 V |
Electric motor connection cable |
1 m, 2 x 0.75 mm² (halogen-free) |
Auxiliary switch connection cable |
1 m, 6 x 0.75 mm² (halogen-free) |
Running time spring |
20 seconds at -10…+55 °С < 60 seconds at -30…-10 °С |
Running time motor |
< 60 s/90° |
Response temperature of thermal breaker sensors |
Duct sensor 72 °С Outdoor sensor 72 °С |
Service life |
Min. 60 000 emergency positions |
Technical maintenance |
Not required |
|
|
MAIN TECHNICAL SPECIFICATIONS OF ZERN ELECTRIC ACTUATORS WITH A RETURN SPRING AND A THERMAL BREAKER |
Technical data |
Basic models |
Rated operation voltage |
AC/DC 24 V |
AC 100-240 V |
Permissible operating voltage tolerance |
AC/DC 19.2…28.8 V |
АС 85…265 V |
AC mains frequency |
50/60 Hz |
Power consumption at rest [W] |
3 |
Power consumption in operation [W] |
5 |
Motor torque [Nm] |
5 |
Spring torque [Nm] |
SEC class |
III |
II |
Ingress protection rating |
IP54 |
Auxiliary switches |
2 pcs., single-pole, reversible, 1 mA…3(0.5)A, AC 220 V |
Electric motor connection cable |
1 m, 2 x 0.5 mm² (halogen-free) |
Auxiliary switch connection cable |
1 m, 6 x 0.5 mm² (halogen-free) |
Running time spring |
< 20 seconds < 60 seconds at -30…-10 °С |
Running time motor |
< 70 s/95° |
Response temperature of thermal breaker sensors |
Duct sensor 72 °С Outdoor sensor 72 °С |
|
|
MAIN TECHNICAL SPECIFICATIONS OF SIEMENS ELECTRIC ACTUATORS WITH A RETURN SPRING AND A THERMAL BREAKER |
Technical data |
Basic models |
Rated operation voltage |
AC 24 V DC 24…48 V |
AC 230 V |
Permissible operating voltage tolerance |
AC/DC ±20% |
АС ±15% |
AC mains frequency |
50/60 Hz |
Power consumption at rest [W] |
2 |
3.5 |
Power consumption in operation [W] |
3.5 |
4.5 |
Maximum design capacity [VA] |
5 |
7 |
Motor torque [Nm] |
4 |
Spring torque [Nm] |
3 |
SEC class |
III |
II |
Ingress protection rating |
IP54 |
Auxiliary switches |
2 pcs., single-pole, reversible, 6(2)A, AC 24...250 V |
Electric motor connection cable |
0.9 m, 2 x 0.75 mm² (halogen-free) |
Auxiliary switch connection cable |
0.9 m, 6 x 0.75 mm² (halogen-free) |
Running time spring |
15 seconds < 60 seconds at -30…-10 °С |
Running time motor |
90 s/90° |
Response temperature of thermal breaker sensors |
Duct sensor 72 °С Outdoor sensor 72 °С |
Service life |
10 000 emergency positions |
Technical maintenance |
Not required |
|