VENTS TT Silent-M 200
Inline mixed-flow fans in sound- and heat-insulated casing with the air flow up to 1020 m³/h.
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional diagrams
- BIM
- Designation key
Description
Description
APPLICATION | |
|
|
DESIGN | |
|
|
|
|
MOTOR | |
|
|
CONTROL | |
|
|
TT Silent-M fan with a three-position speed switch | |
|
|
TT Silent-M fan with a built-in speed controller | |
MOUNTING | |
|
|
THE FAN WITH ELECTRONIC MODULE OF THE TEMPERATURE SENSOR AND SPEED CONTROLLER («U» OPTION) | |
|
|
The front panel of the electronic module has the following control knobs: | |
|
|
The fan is available in two modifications: | |
|
|
CONTROL LOGIC OF THE FAN WITH THE ELECTRONIC TEMPERATURE AND SPEED CONTROL MODULE | |
|
|
There are two switch delay control logics for various cases: | |
|
|
Characteristics
Characteristics
Parameter |
TT Silent-M 200 min |
TT Silent-M 200 max |
Measurement unit |
---|---|---|---|
Speed | min | max | - |
Phase | 1 | 1 | ˜ |
Voltage | 230 | 230 | V |
Frequency | 50/60 | 50/60 | Hz |
Fan power | 78 | 110 | W |
RPM | 2015 | 2445 | min-1 |
Current | 0.35 | 0.49 | A |
Maximum air capacity | 810 | 1020 | m³/h |
Max. transported air temperature | 60 | 60 | °С |
Sound pressure level at 3 m | 31 | 36 | dBА |
Protection rating | IP X4 | IP X4 | - |
Duct diameter | 200 | 200 | mm |
Sound- and heat-insulated casing | yes | yes | - |
Casing material | polymer coated steel | polymer coated steel | - |
Weight | 8 | 8 | kg |
SEC Class | C | C | - |
Duct | for round air ducts | for round air ducts | - |
Type | supply and exhaust | supply and exhaust | - |
Mounting | floor mounting, wall mounting, ceiling mounting, Inline | floor mounting, wall mounting, ceiling mounting, Inline | - |
* | To meet the requirements of ErP 2018, a speed controller and local demand control typology must be applied (connect a sensor). | To meet the requirements of ErP 2018, a speed controller and local demand control typology must be applied (connect a sensor). | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
"TT-M, TT-MD, TT-MD EC, TT Silent-M, TT Silent-MD, TT Silent-MD EC" user's manual 06-2018 (V135EN-03) (pdf 3.41Mb)
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 198 | mm |
B | 293 | mm |
B1 | 386 | mm |
H | 295 | mm |
L | 550 | mm |
Additional diagrams
Additional diagrams
Low speed | Gen. | Octave-frequency band [Hz] | LpA, 3 m dBA | LpA, 1 m dBA | ||||||||
Sound-power level | dBA | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||
LwA to inlet | dBA | 63 | 34 | 53 | 60 | 57 | 56 | 41 | 31 | 17 | 43 | 53 |
LwA to outlet | dBA | 62 | 43 | 46 | 53 | 56 | 58 | 53 | 46 | 36 | 41 | 51 |
LwA to environment | dBA | 52 | 40 | 46 | 46 | 44 | 41 | 37 | 35 | 30 | 31 | 41 |
High speed | Gen. | Octave-frequency band [Hz] | LpA, 3 m dBA | LpA, 1 m dBA | ||||||||
Sound-power level | dBA | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||
LwA to inlet | dBA | 69 | 38 | 59 | 66 | 63 | 62 | 45 | 34 | 18 | 49 | 59 |
LwA to outlet | dBA | 67 | 39 | 44 | 48 | 66 | 58 | 48 | 48 | 32 | 47 | 57 |
LwA to environment | dBA | 57 | 44 | 52 | 52 | 49 | 45 | 41 | 39 | 34 | 36 | 46 |
Designation key
Designation key
|
|
Accessories