VENTS VKH 4E 250
Centrifugal roof fan with horizontal air exhaust and with maximum air flow of up to 820 m³/h.
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional characteristics
- Designation key
Description
Description
APPLICATION
|
DESIGN
|
VKH fan store roof ventilation example |
Characteristics
Characteristics
Parameter |
VKH 4E 250 |
Measurement unit |
---|---|---|
Frequency | 50 | Hz |
Phase | 1 | ˜ |
Power | 48 | W |
Voltage | 230 | V |
A | 0.23 | A |
Air capacity | 820 | m³/h |
EC motor | no | - |
RPM | 1440 | min-1 |
Noise level at 3 m | 46 | dBА |
Design | centrifugal | - |
Motor protection rating | IP44 | - |
Transported air temperature | -25 ... +50 | °С |
IP Code | IP X4 | - |
Number of poles | 4 | - |
SEC Class | B | - |
Weight | 12.1 | kg |
Outdoor mounting | yes | - |
Sound-insulated casing | no | - |
Type | exhaust | - |
Mounting | for roof | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 285 | mm |
∅d | 11 | mm |
A | 451 | mm |
B | 450 | mm |
C | 330 | mm |
H | 237 | mm |
H1 | 244 | mm |
Additional characteristics
Additional characteristics
Sound power level A-weighted | Gen. | Octave-frequency band [Hz] | LpA, 3 m dBA | LpA, 1 m dBA | ||||||||
dBA | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||||
LwA to inlet | dBA | 68 | 51 | 57 | 60 | 52 | 63 | 62 | 57 | 52 | 47 | 57 |
LwA to environment | dBA | 67 | 29 | 48 | 57 | 60 | 63 | 59 | 51 | 37 | 46 | 56 |
Designation key
Designation key
Series and modification | Casing material | Motor modification | Turbine standard size | |
Number of poles | Phase | |||
VENTS VKH: horizontal air exhaust | _: steel with polymeric coating А: aluminum z: galvanized steel |
2 4 6 |
Е: single-phase D: three-phase |
190; 220; 225; 250; 280; 310; 355; 400; 450; 500; 560; 630; 710 |
Accessories