VENTS VKPFI 4E 400*200
Inline centrifugal sound- and heat insulated fan. Maximum capacity - 1440 m3/h.
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional diagrams
- Designation key
Description
Description
APPLICATIONS | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
VENTS VKPFI fan office ventilation example |
Characteristics
Characteristics
Parameter |
VKPFI 4E 400*200 |
Measurement unit |
---|---|---|
Phase | 1 | ˜ |
Voltage | 230 | V |
Frequency | 50 | Hz |
Sound pressure level at 3 m distance | 42 | dBА |
Air capacity | 1440 | m³/h |
Power consumption | 295 | W |
Current | 1.32 | A |
RPM | 1350 | min-1 |
Protection rating | IP X4 | - |
Design | centrifugal | - |
Transported air temperature | -25 ... +40 | °С |
Weight | 29 | kg |
Number of poles | 4 | - |
Sound- and heat-insulated casing | yes | - |
Casing material | galvanized steel | - |
Width | 400 | mm |
Height | 200 | mm |
Duct | for rectangular air ducts | - |
Mounting | Inline | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
В | 400 | mm |
B1 | 420 | mm |
B2 | 440 | mm |
B3 | 470 | mm |
H | 200 | mm |
H1 | 220 | mm |
H2 | 240 | mm |
H3 | 360 | mm |
L | 500 | mm |
Additional diagrams
Additional diagrams
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 66 | 50 | 60 | 58 | 54 | 50 | 49 | 46 | 39 | ||||||||||
LwA to outlet | dBA | 67 | 48 | 60 | 62 | 58 | 60 | 57 | 54 | 49 | ||||||||||
LwA to environment | dBA | 43 | 24 | 35 | 45 | 41 | 36 | 34 | 29 | 22 |
Designation key
Designation key
Series | Motor modification | Flange diameter [W*H] | ||
Number of poles | Phase | |||
VENTS VKPF | I: sound- and heat-insulated casing | 4 6 |
E: single phase D: three phases |
400*200; 500*250; 500*300; 600х300; 600*350; 700*400; 800*500; 900*500; 1000*500 |
Accessories