VENTS VKPFI 6E 600*350
Inline centrifugal sound- and heat insulated fan. Maximum capacity - 2755 m3/h.
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional diagrams
- Designation key
Description
Description
APPLICATIONS | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
VENTS VKPFI fan office ventilation example |
Characteristics
Characteristics
Parameter |
VKPFI 6E 600*350 |
Measurement unit |
---|---|---|
Phase | 1 | ˜ |
Voltage | 230 | V |
Frequency | 50 | Hz |
Sound pressure level at 3 m distance | 43 | dBА |
Air capacity | 2755 | m³/h |
Power consumption | 720 | W |
Current | 3.6 | A |
RPM | 820 | min-1 |
Protection rating | IP X4 | - |
Design | centrifugal | - |
Transported air temperature | -20 … +60 | °С |
Weight | 72 | kg |
Number of poles | 6 | - |
Sound- and heat-insulated casing | yes | - |
Casing material | galvanized steel | - |
Width | 600 | mm |
Height | 350 | mm |
Duct | for rectangular air ducts | - |
Mounting | Inline | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
В | 600 | mm |
B1 | 620 | mm |
B2 | 640 | mm |
B3 | 670 | mm |
H | 350 | mm |
H1 | 370 | mm |
H2 | 390 | mm |
H3 | 530 | mm |
L | 735 | mm |
Additional diagrams
Additional diagrams
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 65 | 52 | 56 | 53 | 53 | 57 | 54 | 54 | 47 | ||||||||||
LwA to outlet | dBA | 68 | 49 | 55 | 56 | 63 | 61 | 56 | 61 | 49 | ||||||||||
LwA to environment | dBA | 50 | 39 | 42 | 46 | 43 | 45 | 43 | 32 | 29 |
Designation key
Designation key
Series | Motor modification | Flange diameter [W*H] | ||
Number of poles | Phase | |||
VENTS VKPF | I: sound- and heat-insulated casing | 4 6 |
E: single phase D: three phases |
400*200; 500*250; 500*300; 600х300; 600*350; 700*400; 800*500; 900*500; 1000*500 |
Accessories
Similar products