VENTS VPA 200-6,0-3
Supply unit with the air flow up to 810 m³/h in the compact sound- and heat-insulated casing with electric heater.
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional characteristics
- Designation key
- Accessories
Description
Description
DESCRIPTION | CASING |
|
|
FILTER | HEATER |
|
|
FAN | |
|
|
CONTROL AND AUTOMATION | |
|
|
CONTROL AND PROTECTION FUNCTIONS | |
|
|
MOUNTING | |
|
|
Characteristics
Characteristics
Parameter |
VPA 200-6,0-3 |
Measurement unit |
---|---|---|
Frequency | 50 | Hz |
Phase | 3 | ˜ |
Voltage | 400 | V |
Fan current | 0.84 | A |
Maximum fan power | 193 | W |
Electric heater power | 6000 | W |
Electric heater current | 8.7 | A |
Air capacity | 810 | m³/h |
Total unit power | 6193 | W |
Total unit current | 9.54 | A |
Number of electrical heating elements | 3 | - |
RPM | 2780 | min-1 |
Transported air temperature | -25 ... +40 | °С |
Sound pressure level at 3 m distance | 30 | dBА |
Heating | electric heating | - |
Casing material | aluzinc | - |
Filter | G4 | - |
Insulation | 25 mm mineral wool | - |
Connected air duct size | 200 | mm |
Weight | 52 | kg |
Duct | for round air ducts | - |
Connection diameter | 200 | mm |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 199 | mm |
B | 487 | mm |
B1 | 526.5 | mm |
H | 513 | mm |
L | 835 | mm |
L1 | 684 | mm |
Additional characteristics
Additional characteristics
Sound-power level | Gen | Octave-frequency band [Hz] | ||||||||
63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||
LWA to inlet | dBA | 65 | 41 | 58 | 59 | 56 | 60 | 62 | 56 | 41 |
LWA to outlet | dBA | 71 | 46 | 57 | 63 | 64 | 66 | 66 | 58 | 45 |
LWA to environment | dBA | 46 | 15 | 31 | 43 | 40 | 34 | 30 | 22 | 8 |
Designation key
Designation key
Series | Air duct diameter | Electric heater power [kW] | Phase | Integrated control system | ||||
VENTS VPA | – | 1: high-powered motor | 100; 125; 150; 200; 250; 315 | – | 1.8; 2.4; 3.4; 3.6; 5.1; 6; 9 | – | 1: single phase 3:three phase |
LCD: integrated automation with A16 control panel |
Accessories
Accessories
Type | Replaceable filter | Filter type |
VPA 100-1,8-1 | SF 335x322x70 G4 | panel filter |
VPA 125-2,4-1 | ||
VPA 150-2,4-1 | SF 397x364x70 G4 | panel filter |
VPA 150-3,4-1 | ||
VPA 150-5,1-3 | ||
VPA 150-6,0-3 | ||
VPA 200-3,4-1 | SF 439x428x70 G4 | panel filter |
VPA 200-5,1-3 | ||
VPA 200-6,0-3 | ||
VPA 250-3,6-3 | ||
VPA 250-6,0-3 | ||
VPA 250-9,0-3 | ||
VPA 315-6,0-3 | SF 475x470x70 G4 | panel filter |
VPA 315-9,0-3 | ||
VPA-1 315-6,0-3 | ||
VPA-1 315-9,0-3 |
Accessories
Similar products