VENTS VUT 180 P5
Heat recovery air handling unit in sound- and heat-insulated casings. Air flow up to 220 m³/h. Heat recovery efficiency up to 98 %.
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional characteristics
- Designation key
- Accessories
Description
Description
DESCRIPTION | |||||
|
|
||||
FILTER | CASING | ||||
|
|
||||
FANS | |||||
|
|
||||
HEAT EXCHANGER | |||||
|
|
||||
CONTROL AND AUTOMATION | |||||
|
|
||||
FREEZE PROTECTION | INSTALLATION | ||||
|
|
||||
UNIT DESIGN | |||||
APPLICATION OPTIONS | |||||
Characteristics
Characteristics
Parameter |
VUT 180 P5 |
Measurement unit |
---|---|---|
Frequency | 50/60 | Hz |
Phase | 1 | ˜ |
Voltage | 230 | V |
Maximum unit power | 117 | W |
Maximum unit current | 0.54 | A |
Sound pressure level at 3 m distance | 35 | dBА |
Air capacity | 220 | m³/h |
RPM | 2317 | min-1 |
Heat recovery efficiency | 86...98 | % |
Transported air temperature | -25 ... +60 | °С |
Casing material | expanded polypropylene | - |
Insulation | EPP 30-15 mm | - |
Filter: extract | G4 | - |
Filter: supply | G4 (F7*) | - |
Connected air duct size | 150 | mm |
Weight | 14 | kg |
Heat exchanger type | counter-flow | - |
Heat exchanger material | polystyrene | - |
SEC Class | D | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 150 | mm |
B | 600 | mm |
B2 | 326 | mm |
H | 264 | mm |
L | 900 | mm |
Additional characteristics
Additional characteristics
A-weighted sound power level | Total | Octave frequency band [Hz] | LpA, 3 m dBA | LpA, 1 m dBA | ||||||||
dBA | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||||
LwA to supply air inlet | dBA | 59 | 27 | 46 | 54 | 55 | 53 | 48 | 44 | 35 | ||
LwA to supply air outlet | dBA | 60 | 27 | 46 | 54 | 55 | 52 | 49 | 44 | 35 | ||
LwA to supply air outlet | dBA | 55 | 25 | 41 | 50 | 51 | 44 | 42 | 39 | 30 | ||
LwA to exhaust air outlet | dBA | 55 | 26 | 41 | 51 | 51 | 44 | 42 | 39 | 31 | ||
LwA to environment | dBA | 54 | 18 | 36 | 47 | 49 | 48 | 43 | 37 | 33 | 33 | 43 |
Calculation of air temperature downstream of the heat exchanger:
t = toutd + khr * (textr - toutd) / 100,
where
toutd – outdoor air temperature °С
textr – extract air temperature °С
khr – heat exchanger efficiency (according to the diagram) [%]
Designation key
Designation key
Accessories
Accessories
Model | G4 panel supply filter | F7 panel supply filter |
VUT 180 P5 | SF 214 x 186 х 18 G4 | SF 214 x 186 x 48 F7 |
VUE 180 P5 |