VENTS KSA 160-2E
- Description
- Characteristics
- Downloads
- Dimensions
- Additional diagrams
- Designation key
APPLICATIONS | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
THE FAN WITH ELECTRONIC TEMPERATURE AND CONTROL MODULE (U OPTION)
|
|
|
|
|
|
Control logic of the fan with the electronic temperature and speed control module
|
|
|
|
There are three switch delay patterns for various cases: | |
|
|
VENTS KSA fan greenhouse ventilation example |
Parameter |
KSA 160-2E |
Measurement unit |
---|---|---|
Phase | 1 | ˜ |
Voltage | 230 | V |
Frequency | 50 | Hz |
Sound pressure level at 3 m distance | 37.9 | dBА |
Power consumption | 335 | W |
RPM | 2600 | min-1 |
Maximum air capacity | 730 | m³/h |
Current | 1.16 | A |
Max. transported air temperature | -25 +40 | °С |
Protection rating | IP X4 | - |
Design | centrifugal | - |
Weight | 6.28 | kg |
Duct diameter | 160 | mm |
Number of poles | 2 | - |
Sound- and heat-insulated casing | yes | - |
Casing material | aluzinc | - |
SEC Class | C | - |
Duct | for round air ducts | - |
Type | supply and exhaust | - |
Mounting | Inline | - |
Parameter | Value | Measurement unit |
---|---|---|
∅D | 158 | mm |
B | 231 | mm |
H | 343 | mm |
Р | 48 | mm |
L | 358 | mm |
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 56 | 44 | 51 | 48 | 38 | 33 | 29 | 24 | 22 | ||||||||||
LwA to outlet | dBA | 54 | 42 | 51 | 50 | 37 | 31 | 30 | 25 | 25 | ||||||||||
LwA to environment | dBA | 49 | 37 | 47 | 43 | 34 | 28 | 25 | 20 | 18 |
Series | Spigot diameter | Polarity | Phase | Options |
VENTS KSA | 100; 125; 150; 160; 200 | 2, 4 | Е: single phase | U: speed controller with an electronic thermostat and a temperature sensor integrated inside an air duct. Temperature-based operation logic. Un: speed controller with an electronic thermostat and a temperature sensor fixed on a 4-meter cable. Temperature-based operation logic. U1: speed controller with an electronic thermostat and a temperature sensor integrated inside an air duct. Timer-based operation logic. U1n: speed controller with an electronic thermostat and a temperature sensor fixed on a 4-meter cable. Timer-based operation logic. U2: speed controller with an electronic thermostat and a temperature sensor integrated inside an air duct. Temperature-based switching on/off. U2n: speed controller with an electronic thermostat and a temperature sensor fixed on a 4-meter cable. Temperature-based switching on/off. R1: power cord with a mains plug. P: integrated smooth speed controller. |