Parameter |
KSB 100 50 Hz |
KSB 100 60 Hz |
Measurement unit |
---|---|---|---|
Phase | 1 | 1 | ˜ |
Voltage | 230 | 230 | V |
Frequency | 50 | 60 | Hz |
Sound pressure level at 3 m distance | 33 | 34 | dBА |
Power consumption | 73 | 77 | W |
Maximum air capacity | 240 | 255 | m³/h |
RPM | 2560 | 2690 | min-1 |
Current | 0.32 | 0.34 | A |
Max. transported air temperature | -25...+55 | -25...+55 | °С |
Protection rating | IP X4 | IP X4 | - |
Design | centrifugal | centrifugal | - |
Weight | 5.4 | 5.4 | kg |
Duct diameter | 100 | 100 | mm |
Sound- and heat-insulated casing | yes | yes | - |
Casing material | galvanized steel | galvanized steel | - |
SEC Class | C | C | - |
Duct | for round air ducts | for round air ducts | - |
Type | supply and exhaust | supply and exhaust | - |
Mounting | Inline | Inline | - |
Parameter | Value | Measurement unit |
---|---|---|
∅D | 99 | mm |
B1 | 280 | mm |
H | 192 | mm |
B | 322 | mm |
L | 447 | mm |
L1 | 380 | mm |
L2 | 350 | mm |
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 59 | 53 | 57 | 54 | 52 | 51 | 54 | 51 | 47 | ||||||||||
LwA to outlet | dBA | 68 | 49 | 50 | 53 | 56 | 66 | 63 | 56 | 54 | ||||||||||
LwA to environment | dBA | 40 | 27 | 29 | 32 | 31 | 34 | 29 | 29 | 20 |
Series | Spigot diameter | Options |
VENTS KSB |
100; 125; 150; 160; 200; 250; 315 | R - power cord with IEC C14 electric plug; S - high-powered motor; M – anti-vibration mount; U - speed controller with electronic thermostat and temperature sensor integrated into the air duct. Equipped with power cord and IEC C14 electric plug. Temperature-based operation logic; Un -speed controller with electronic thermostat and external temperature sensor fixed on 4 m cable. Equipped with power cord and IEC C14 electric plug. Temperature-based operation logic; U1 - speed controller with electronic thermostat and temperature sensor integrated into the air duct. Equipped with power cord and IEC C14 electric plug. Timer-based operation logic; U1n - speed controller with electronic thermostat and external temperature sensor fixed on 4 m cable. Equipped with power cord and IEC C14 electric plug. Timer-based operation logic. |