VENTS PA 01 W4
Suspended air supply unit with the air flow up to 1200 m³/h in the sound- and heat-insulated casing with the water heater
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional characteristics
- Hot water coil parameters
- Designation key
- Accessories
Description
Description
DESCRIPTION | CASING |
|
|
FILTER | HEATER |
|
|
FAN | |
|
|
MOUNTING | |
|
|
CONTROL AND AUTOMATION | |
|
|
CONTROL AND PROTECTION FUNCTIONS | |
|
|
SUPPLEMENTARY EQUIPMENT | |
|
|
Characteristics
Characteristics
Parameter |
PA 01 W4 |
Measurement unit |
---|---|---|
Frequency | 50 | Hz |
Phase | 3 | ˜ |
Voltage | 400 | V |
Fan current | 0.55 | A |
Maximum fan power | 320 | W |
Air capacity | 1200 | m³/h |
Total unit power | 320 | W |
Total unit current | 0.55 | A |
RPM | 2700 | min-1 |
Filter | G4 (F7) pocket type* | - |
Transported air temperature | -25 ... +40 | °С |
Sound pressure level at 3 m distance | 51 | dBА |
Casing material | aluzinc | - |
Heating | water heating | - |
Insulation | 50 mm mineral wool | - |
Connected air duct size | 400х200 | mm |
Number of water (glycol) coil rows | 4 | - |
Width | 400 | mm |
Weight | 57 | kg |
Height | 200 | mm |
Duct | for rectangular air ducts | - |
* | option | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
"Control and automation block for VENTS PA...W" user's manual 06-2018 (V43(automatic)EN-06) (pdf 1.61Mb)
"Control system for air supply and air handling units based on Freemax controllers and AC208A2 sensor control panels" user's manual 07-2023 (V99EN-03) (pdf 7.14Mb)
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
B | 400 | mm |
B1 | 420 | mm |
B2 | 624 | mm |
B3 | 582 | mm |
H | 200 | mm |
H1 | 220 | mm |
H2 | 374 | mm |
L | 1145 | mm |
L1 | 1106 | mm |
Additional characteristics
Additional characteristics
Sound-power level | Gen | Octave-frequency band [Hz] | ||||||||
63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||
LWA to inlet | dBA | 62 | 47 | 62 | 58 | 54 | 43 | 45 | 44 | 37 |
LWA to outlet | dBA | 73 | 49 | 61 | 70 | 70 | 62 | 63 | 61 | 57 |
LWA to environment | dBA | 47 | 24 | 39 | 44 | 46 | 33 | 35 | 27 | 19 |
Hot water coil parameters
Hot water coil parameters
How to use water heater diagrams
System Parameters: Air flow = 950 m³/h. Outside air temperature = -15 °C. Water temperature (in/out) = 70/50 °C.
- Air Speed. Starting from 950 m³/h on the air flow scale draw a vertical line ① till the air speed axis which makes about 3.35 m/s.
- Supply air temperature. Prolong the line ① up to the point where it crosses the outside air temperature (blue curve, e.g. -15 °C); then draw a horizontal line ② from this point to the left till crossing water in/out temperature curve (e.g. 70/50 °C). From this point draw a vertical line ③ to the supply air temperature axis on top of the graphic (+29 °C).
- Heating coil capacity. Prolong the line ① up to the point where it crosses the outside air temperature (e.g. -15 °C, red curve) and draw a horizontal line ④ from this point to the right until it crosses water in/out temperature curve (e.g. 70/50 °C), from here draw a vertical line ⑤ up to the scale representing the heating coil capacity (16.0 kW).
- Water flow. Prolong the line ⑤ down to water flow axis at the bottom of the graphic ⑥ (0.2 l/s).
- Water pressure drop. Draw the line ⑦ from the point where the line ⑥ crosses the black curve to the pressure drop axis (2.1 kPa).
Designation key
Designation key
Series | Unit standard size | Heater type | Row number of the heater | Integrated control system |
VENTS PA | 01; 02; 03; 04 | W: water | 2: two rows; 3: three rows; 4: four rows |
LCD: integrated automation with A13 control panel |
Accessories
Accessories
Type | G4 replaceable filter | F7 replaceable filter | Filter type |
PA 01 W2 | SFK 474x269x27 G4 | SFK 474x269x27 F7 | pocket filter |
PA 01 W4 | |||
PA 02 W2 | SFK 538x342x27 G4 | SFK 538x342x27 F7 | pocket filter |
PA 02 W4 | |||
PA 03 W2 | SFK 637x395x27 G4 | SFK 637x395x27 F7 | pocket filter |
PA 03 W4 | |||
PA 04 W2 | SFK 737x441x27 G4 | SFK 737x441x27 F7 | pocket filter |
PA 04 W3 |
Accessories
Similar products