DESCRIPTION |
CASING |
- The PA unit is a ready to use ventilation unit for air filtration, warming and supply to the room.
|
- Steel casing covered with aluzinc coating internally filled with 50 mm heat- and sound-insulating layer made of mineral wool.
|
FILTER |
HEATER |
- Integrated panel G4 filter ensures sufficient supply air purification (optionally F7).
|
- The PA units are equipped with water heater.
- Depending on the required heating capacity the water heaters are available in two-, three- or four-row modifications.
- The water heaters are designed for max. operating pressure 1.0 MPa (10 bar) and max. operating temperature 95 °C of the heat medium.
|
FAN |
- The unit is equipped with a direct-driven centrifugal fan with backward curved blades and external rotor motor.
- The fan configuration ensures the best operating characteristics: high air flow and efficiency combined with low noise level.
|
MOUNTING |
|
- The unit is designed for indoor installation either on the floor, on the wall or under the ceiling by means of a seat angle with inserted vibration-damping element or attached to a wall with brackets.
- The unit can be mounted either in service spaces or in main premises above the suspended ceiling, in the pocket or the unit can be placed directly in the room.
- All the electrical connections are performed through the terminal box placed in the connection box.
- PA supply units are supplied with the fastening brackets to facilitate mounting.
|
- The unit can be mounted in any position but the vertical one with vertical air downstream because the electrical heating elements are not allowed under the fan.
- Access for the unit maintenance and filter cleaning shall be provided.
- The PA...W unit design enables to lead the water heater pipes to the right or to the left while mounting.
- The pipes are directed on the right on supply air side by default.
|
CONTROL AND AUTOMATION |
|
- Integrated control and automation system for speed (air flow) control and setting supply air temperature.
|
- The unit may be remotely controlled from the external control panel fixed on wire.
|
CONTROL AND PROTECTION FUNCTIONS |
|
- Control from the control panel: switching the unit on/off, fan speed selection (low/medium/high speed), selecting heating/cooling modes (if connected to duct cooler).
- Maintaining supply air temperature set from the control panel by controlling the circulation pump and actuating the heat medium regulating valve; input from the heat medium flow switch (pump alarm).
- Safe start-up/ shutdown of the fans, warming up of the water heater before start-up; return heat medium temperature control when the fan is off.
|
- Freezing protection of the water heating coils by the exhaust temperature sensor and the return heat medium temperature sensor.
- Control of the compressor and condensing unit of the water cooler by the room temperature sensor (for the models equipped with a duct air cooler).
- Filter clogging degree with differential pressure sensor.
- Actuating the external air damper with a return spring.
- Unit shut down at signal from the fire alarm system.
|
SUPPLEMENTARY EQUIPMENT |
|
- The mixing units USWK are recommended for smooth supply air temperature regulation in the units equipped with water heaters.
- The mixing unit USWK with three-way heat medium regulating valve and circulation pump provides smooth heating capacity regulation and minimizes the water heater freezing danger.
- To disable uncontrollable air flow when the fan is off it is recommended to install the air damper with servo actuator from outside at the unit inlet.
|
- To protect the water heater against cold intake air in case of power failure for the units with water heaters (PA...W) it is recommended to install the air damper with a return spring.
- For attenuation of sound generated by the fan it is recommended to install the duct silencer (refer SR).
- For vibration absorbing it is recommended to install the flexible anti-vibration connectors (refer VVG) on both sides of the unit.
|