Characteristics
Characteristics
Parameter |
VKPI 2E 500*250 50 Hz |
VKPI 2E 500*250 60 Hz |
Measurement unit |
---|---|---|---|
Phase | 1 | 1 | ˜ |
Voltage | 230 | 230 | V |
Frequency | 50 | 60 | Hz |
Sound pressure level at 3 m distance | 51 | 52 | dBА |
Air capacity | 1720 | 1850 | m³/h |
Power consumption | 305 | 380 | W |
Current | 1.32 | 1.65 | A |
RPM | 2550 | 2830 | min-1 |
Protection rating | IP X4 | IP X4 | - |
Design | centrifugal | centrifugal | - |
Transported air temperature | -25 ... +45 | -25 ... +45 | °С |
Weight | 27.6 | 27.6 | kg |
Number of poles | 2 | 2 | - |
Sound- and heat-insulated casing | yes | yes | - |
Casing material | galvanized steel | galvanized steel | - |
Width | 500 | 500 | mm |
Height | 250 | 250 | mm |
Duct | for rectangular air ducts | for rectangular air ducts | - |
Mounting | Inline | Inline | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
В | 500 | mm |
B1 | 520 | mm |
B2 | 540 | mm |
B3 | 600 | mm |
H | 250 | mm |
H1 | 270 | mm |
H2 | 290 | mm |
H3 | 410 | mm |
L | 640 | mm |
Additional diagrams
Additional diagrams
Sound power level, A-filter applied | Sound pressure level at 3 meters, A-filter applied | Sound pressure level at 1 meters, A-filter applied | ||||||||||
General | Octave frequency band [Hz] | |||||||||||
Hz | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | LpA, 3 m [dBA] | LpA, 1 m [dBA] | ||
LwA to inlet | dBA | 88 | 74 | 82 | 84 | 71 | 75 | 78 | 76 | 70 | 67 | 77 |
LwA to outlet | dBA | 91 | 74 | 78 | 83 | 81 | 85 | 83 | 83 | 76 | 70 | 80 |
LwA to environment | dBA | 72 | 40 | 56 | 68 | 68 | 66 | 60 | 54 | 44 | 52 | 62 |
Designation key
Designation key
Series | Motor modification | Flange diameter [W*H] | ||
Number of poles | Phase | |||
VENTS VKP | I:sound- and heat-insulated casing | 2 4 |
E: single phase D: three phase |
400*200; 500*250; 500*300; 600*300; 600*350; 1000*500 |