VENTS VKPI 4D 500*300
Inline centrifugal sound- and heat insulated fan. Maximum capacity - 1620 m3/h.
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional diagrams
- Designation key
Description
Description
APPLICATIONS | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
Characteristics
Characteristics
Parameter |
VKPI 4D 500*300 50 Hz |
VKPI 4D 500*300 60 Hz |
Measurement unit |
---|---|---|---|
Phase | 3 | 3 | ˜ |
Voltage | 400 | 400 | V |
Frequency | 50 | 60 | Hz |
Sound pressure level at 3 m distance | 47 | 50 | dBА |
Air capacity | 1380 | 1620 | m³/h |
Power consumption | 136 | 165 | W |
Current | 0.34 | 0.53 | A |
RPM | 1360 | 1600 | min-1 |
Protection rating | IP X4 | IP X4 | - |
Design | centrifugal | centrifugal | - |
Weight | 37.2 | 37.2 | kg |
Transported air temperature | -25 … +65 | -25 ... +55 | °С |
Number of poles | 4 | 4 | - |
Sound- and heat-insulated casing | yes | yes | - |
Casing material | galvanized steel | galvanized steel | - |
Width | 500 | 500 | mm |
Height | 300 | 300 | mm |
Duct | for rectangular air ducts | for rectangular air ducts | - |
Type | exhaust, supply | exhaust, supply | - |
Mounting | Inline | Inline | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
В | 500 | mm |
B1 | 520 | mm |
B2 | 540 | mm |
B3 | 600 | mm |
H | 300 | mm |
H1 | 320 | mm |
H2 | 340 | mm |
H3 | 460 | mm |
L | 680 | mm |
Additional diagrams
Additional diagrams
Sound power level, A-filter applied | Sound pressure level at 3 meters, A-filter applied | Sound pressure level at 1 meters, A-filter applied | ||||||||||
General | Octave frequency band [Hz] | |||||||||||
Hz | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | LpA, 3 m [dBA] | LpA, 1 m [dBA] | ||
LwA to inlet | dBA | 77 | 59 | 67 | 69 | 61 | 73 | 71 | 67 | 61 | 56 | 66 |
LwA to outlet | dBA | 81 | 56 | 67 | 71 | 71 | 75 | 75 | 74 | 69 | 61 | 71 |
LwA to environment | dBA | 68 | 46 | 57 | 63 | 60 | 60 | 59 | 55 | 50 | 47 | 57 |
Designation key
Designation key
Series | Motor modification | Flange diameter [W*H] | ||
Number of poles | Phase | |||
VENTS VKP | I:sound- and heat-insulated casing | 2 4 |
E: single phase D: three phase |
400*200; 500*250; 500*300; 600*300; 600*350; 1000*500 |
Accessories